Microsoft 365 Copilot

7. Assessment and Calculation

The calculation components and their outputs.

7.1 Token Energy Calculation

Each row in the usage reports is associated with electricity consumption due to the processing of input, cached input, and output tokens. A different amount of each of these token types were measured for different M365 Copilot actions (quantified in the usage report columns). To calculate the IT electricity in kWh consumed for a given row in the usage report, the energy consumed for the token processing of each action is multiplied by the total count of each action taken, and summed over all action types. Cached input tokens include the context re-sent from earlier messages including the system prompt and the multiple assumed agent model calls. Where a row counts Agent Sessions, the per-session energy is calculated from the Token Profile of a whole session.

The training energy of the model is accounted for within the input and output rates, as the AI token methodology includes the Training Energy Uplift in the per-token energy it publishes.

7.2 Facility Energy and Emissions Calculation

Usage Electricity Consumption, being the TFE of the row in kWh, is calculated by multiplying the IT electricity of each row by the PUE factor for the location the row is attributed to under Section 6.5.

UE in tonnes CO₂e are then calculated by multiplying Usage Electricity Consumption by the GCI for the attributed location and the row's date. That calculation is the location-based method of the GHG Protocol Scope 2 Guidance. UE then take a Greenpixie uplift for Scope 1 emissions at the data centre.

7.3 Embodied Emissions Calculation

The embodied emissions associated with each prompt/action are calculated from the Token Profile of each, multiplied by the embodied emissions per token rates provided by the AI token methodology. This is done in the same way as for energy attribution, including for cached token reads.

An allocation for data centre shell construction is then added, in proportion to the row's Usage Electricity Consumption, following the treatment in the cloud methodology. Total Combined Emissions for the row, in tonnes CO₂e, are the sum of UE and Embodied Emissions.

7.4 Water Consumption Calculation

Water consumption is estimated in two parts that are calculated separately and reported as separate figures. The first is IT Cooling Water Consumption, being the water consumed on site in cooling the inference hardware, estimated in litres as the WUE of the attributed location multiplied by the IT electricity of the row before facility overhead. The second is Electricity Generation Water Consumption, being the water consumed in generating the electricity the row draws, estimated in litres as the water intensity factor of the attributed location multiplied by the row's Usage Electricity Consumption. Both components are calculated on a location-based basis. Water withdrawal is outside this methodology.